Precision Cooling for Quantum Infrastructure

At Data Center World, we were approached by an engineer from Aramco with a specific challenge.

A quantum computing installation required a stable 15 °C water supply. The existing infrastructure delivered 10 °C. The system had to bridge that gap without structural rebuild or interruption to ongoing operations.

The question was simple:

Can you convert 10 °C supply water into 15 °C with a flow of 3 m³/h at 1.3 bar differential pressure – reliably, and with precision?

Within weeks, we designed a modified Cooling Distribution Unit capable of delivering up to 5 bar and 5 m³/h, incorporating targeted design adjustments to improve precision and control.

We manufactured the unit and shipped it directly to Saudi Arabia. Installation was carried out by the customer’s engineers, supported remotely by our team.

No local presence was required.

During commissioning, a monitoring-board issue was identified and corrected. The thermal control architecture itself performed as designed from first activation.

The CDU has now operated continuously for four months, maintaining supply temperature within ±0.1 °C.

In quantum computing environments, temperature stability is not an optimisation target – it is a prerequisite.

The project reflects a central principle of our approach:

When system architecture is understood at thermodynamic and hydraulic level, precision is achieved through control – not through excess infrastructure or unnecessary complexity.

It requires engineers who enter the customer’s context, question assumptions, and allow the solution to take shape through dialogue.

NGC took time to understand the challenge before proposing the solution

Managing Density Within Physical Limits

A customer approached us when their server room began to overheat. Newly installed servers delivered higher performance – and significantly higher heat density – than the space had been designed to manage.

We proposed rear-door cooling as an alternative

Ceiling height prevented additional fan coils. A downflow CRAH solution was considered, but could not be accommodated. In-row cooling was evaluated, yet available whitespace was limited.

The installation centred on a 42U, 800 mm rack with a 50 kW load. Room temperature was maintained at 23 °C. Server exhaust air was estimated at 45 °C.

We implemented an RDHx with integrated circulation pump, combined with a dry cooler and chiller in a single fluid circuit. The system was engineered to balance airflow, pressure drop, and return temperature – avoiding excessive fan or pump energy while maintaining stable thermal behaviour.

At maximum load, fan power was 735 W and pump consumption 95 W. Under realistic operating conditions, indoor pPUE (partial Power Usage Effectiveness) was 1.0136.

Including dry cooler and chiller operation, total cooling sub-system pPUE reached 1.0294. The dry cooler handled 94% of annual cooling demand based on local ambient temperature data.

  • The solution required no structural rebuild.
  • It stabilised rack-level thermal behaviour.
  • It reduced energy consumption without increasing system complexity.

NGC understood our constraints – and engineered an energyefficient cooling system to match.

Cookie Policy

What is a cookie?

A cookie is a small datafile that is saved on your computer, tablet or mobile phone. A cookie is not a program that can contain harmful programs or viruses.

How/why the homepage uses cookies

Cookies are necessary for the homepage to function. Cookies help us get an overview of your visit to the homepage so that we can continually optimise and adjust the homepage to your requirements and interests. For example, cookies remember what you might have added to a shopping cart, if you have previously visited the page, if you are logged in and what languages and currency you want displayed on the homepage. We also use cookies to target our ads to you on other homepages. On a very general level, cookies are used as part of our services in order to show content that is as relevant as possible to you.

How long are cookies saved?

How long cookies are saved on your device can vary. The time when they are scheduled to expire is calculated from the last date you visited the homepage. When cookies expire, they are automatically deleted. You can view a complete list of cookies below.

This is how you can reject or delete your cookies

You can always reject cookies on your computer, tablet or phone by changing your browser settings. Where these settings can be found depends on the type of browser you are using. If you do change the settings, please be aware that there will be some functions and services that you cannot use because they rely on the homepage being able to remember the choices you have made.

You can choose to not receive cookies from Google Analytics here.

Deleting cookies

You can delete cookies that you have previously accepted. If you are using a PC with a recent version of a browser, you can delete your cookies by using these shortcut keys: CTRL + SHIFT + Delete.

If the shortcut keys do not work and/or you are using an Apple computer, you must find out what browser you are using and then click on the relevant link:

Remember: If you are using several different browsers, you must delete the cookies in all of them.