NGC’s New 1.5 MW Coolant Distribution Unit
Up to 1.5 MW of cooling through a single unit, with no built-in pump and a maximum of 100 W. That is three times the capacity of our previous largest CDU, built for multi-megawatt data centres.
Why size matters at system level
As AI and high-density racks push data centres towards multi-megawatt cooling loads, the number of CDUs in a system becomes a design question in its own right. Every additional unit adds connections, controls and floor space. A CDU that carries 1.5 MW lets the facility side of the cooling system stay simpler: fewer units, fewer interfaces and one defined point between rack-level cooling and the facility’s cooling source.
What the numbers mean in operation
The 1.5 MW Passive CDU delivers a secondary flow of up to 60 m³/h with a pressure drop of 0.2 bar through DN100 connections. Its capacity is rated at 40 °C inlet and 18 °C outlet. The higher the return temperature the system allows, the more of the year the facility can run on free cooling. We explain the physics in The chiller that uses 42 % of the power for 2.3 % of the cooling.
Under changing load, an ultra-fast modulated valve takes the CDU from idle to full load in 6 to 8 seconds. The CDU predicts the new operating point and reacts 2 to 4 seconds before warmer fluid reaches it. The supply temperature to the racks stays within its limits while the load moves.

Designed for long operation
The 1.5 MW Passive CDU contains no components that require service. A yearly inspection is recommended. It integrates with building management systems via Modbus TCP, SNMP and BACnet, with Redfish available on demand, and can be supplied with dual power supply for redundancy.
Explore it
See the 1.5 MW Passive CDU in 360° on the product page, look inside the unit in the interactive feature guide, or download the datasheet.