What Viborg Can Teach Us About Data Centre Heat Pumps

How much electricity does a data centre heat pump need to turn surplus heat into district heating? Mostly, it depends on one number: the temperature of the water leaving the data centre. Viborg Varme expects a heat pump COP of about 5 when it lifts 30 to 42 °C water from Apple’s data centre and Energinet’s substation to 70 °C. That means about 80 % of the delivered heat comes from surplus heat and 20 % from electricity (Dansk Fjernvarme, April 2026).

Our LinkedIn post about Viborg drew more questions than anything we have published. Here are the answers.

What is happening in Viborg?

From the second half of 2027, Viborg Varme will take surplus heat from Apple’s data centre and Energinet’s transformer station at Tjele. The first stage is 12 MW, with a potential of up to 69 MW over time. Storage tanks will receive the 30 to 42 °C water every day of the year before an isobutane heat pump raises it to 70 °C (Dansk Fjernvarme). Viborg Varme puts its investment at DKK 210 million and expects surplus heat to cover half of its heat supply in 2027 (Dansk Fjernvarme, October 2026).

Why does the lift decide the COP of a data centre heat pump?

The bigger the temperature gap, the more work the compressor does for each kWh of heat. Physics sets a ceiling: the theoretical maximum COP is the network temperature divided by the lift, both in kelvin. Lifting 42 °C water to 70 °C gives a ceiling of about 12. Lifting 30 °C water gives about 8.6. Real machines reach only part of that ceiling, so an expected COP of about 5 sits well below it.

A COP of 5 means that 1 kWh of electricity plus 4 kWh of surplus heat gives 5 kWh of district heat. That is where the 80 % comes from.

Is “80 % free” heat really free?

No. As one reader pointed out, electricity is worth more than heat. The 80 % describes energy, not cost. The utility still pays for pipes, heat pumps, electricity and operation. For the business case, this is the point: every degree of lift you remove is electricity you do not have to buy for the lifetime of the plant.

How warm can the water from a data centre be?

It depends on the cooling technology and on how warm the servers run. Typical return temperatures in Danish data centres are:

  • Room cooling (CRAH/CRAC): around 12 °C
  • Rear-door heat exchangers: 20 to 34 °C
  • Direct-to-chip cooling: around 42 °C
  • The newest NVIDIA generation (Rubin): around 45 °C

Against a 70 °C network, that is the difference between a lift of almost 60 degrees and a lift of 25.

Do servers have to be special to deliver 56 °C water?

This was the most common question. ASHRAE recommends 18 to 27 °C at the server inlet for the best long-term reliability. The allowable range is wider: up to 32 °C for class A1 and up to 45 °C for class A4 (ASHRAE TC 9.9, Thermal Guidelines, 5th edition).

A return temperature near 56 °C requires air leaving the servers at around 60 °C, so the servers must run at the warm end. That is a deliberate choice to make with the IT supplier. Several readers noted that cooler chips tend to last longer. That trade-off is real and belongs in the decision.

Who cools the data centre when the heat is not needed?

In Viborg, the heat utility takes the heat but delivers no cooling in return (Viborg Varme, presentation to the Danish Parliament’s Energy Committee). The data centre must still cool itself. Readers also suggested low-temperature networks for new homes, where less of the heat needs lifting. The whole chain from server to radiator must be optimised, not one link.

Does liquid cooling change the calculation?

It delivers warmer water, so the lift shrinks. In Sønderborg, the Bitten AI supercomputer at the University of Southern Denmark uses liquid cooling to recover all its waste heat for the town’s district heating network (Al Jazeera, November 2026). Recovered heat still only has value where a network can take it.

What have we learned at NGC?

In the solutions we design, supply and return are typically 18 to 22 °C and 38 °C when server exhaust air is 45 °C. Return can reach up to 56 °C when exhaust air is 60 °C. Lifting 56 °C water to 70 °C is half the lift of 42 °C water.

Higher return temperature also means lower flow, less infrastructure and more hours of free cooling. But surplus heat is only valuable when temperature, flow, distance and system design fit together, as we described in The Value of Hot Water and Data Centre Heat Reuse: Kalundborg, Ølgod and the Cost of Distance. Read more about RDHx Active Flow.

FAQ

What COP can a heat pump reach on data centre heat?

It depends mainly on the lift. Viborg Varme expects about 5 when lifting 30 to 42 °C water to 70 °C.

Can data centre heat be used without a heat pump?

Only where the network runs close to the temperature of the water, such as low-temperature networks for new buildings. A 70 °C network like Viborg’s needs a heat pump.

Sources

This article builds on Ole Kristensen’s LinkedIn post about Viborg and the questions in its comments.

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.